Search
Product Categories
NOTE: Indicated PRICES and/or PROMOS on this website are applicable to Metro Manila only.


GST104A
- Description
- Specifications
Conventional Fire Alarm Panel GST-104
GST104A conventional fire control panels provide four zones of fire detection. All panels have been designed to offer high standards of performance, reliability and quantity and comply fully with BS5839, Part 4, 1988 and EN 54 parts 2 and 4.
Features
- Connecting with conventional detectors and manual call points, generating alarm in case of fire, to save human life.
- Every detection zone can have at most 15 conventional detectors. The total number of detectors and call points in a zone shall not exceed 32.
- Sounder outputs, Alarm output and Fault output are available for connecting into other systems.
- Integrated charger and battery management program, fully comply with latest EN54-4 standard requirement.
- Easy operation to enable/disable zones, sounder outputs and alarm output.
- Alarm Test function selectable with or without sounder notification.
- Output programmable for interlink between zones and sounder outputs, alert or evacuate tone, with or without delay.
- Day/Night mode selectable.
- Different Silence/Reset/Test modes can be selected to meet local requirement.
- Three access levels settable via key control.
- Reserved repeater panel interface for fire alarm indication of multiple zones.
Name | Details |
Operating voltage | 220/230VAC ± 15% , 50/60Hz |
Operating Current | 0.35A |
Standard | EN 61000-6-3 EN 61000-3-2 EN 61000-3-3 EN 50130-4 EN 54 part 2 and part 4 |
Approval | LPCB |
Operating Environment | 0°C to 40°C 95% relative humidity |
Standby Batteries | 7AH/24VDC |
Output Voltage | 20VDC to 28 VDC |
Alarming Resistance | 150Ω-1.5KΩ ( nominal 470Ω) |
End of Line | 4.7KΩ or AEOL ( Active End of Line) |
Sounder Output | QTY: 4 (2 for GST102A) Active Mode: 20VDC ~ 28VDC, Output current: 300mA Relay Mode: NO/NC Contact, 1A/24VDC |
Fire Alarm Output | QTY: 1 Active Mode: 20VDC ~ 28VDC, Output current: 300mA Relay Mode: NO/NC Contact, 1A/24VDC |
Fault Output Capacity | QTY: 1 Passive contact output :1A/24VDC |
Aux. Power Output | 20VDC ~ 28VDC , 500mA |
Application | Indoor use |
Dimension | 380mm x 320mm x 103mm |
Model | GST102 | GST104A | GST108 | GST116 |
Detection Zone | 2 | 4 | 8 | 16 |
Sounder Outputs | 2 | 4 | 4 | 4 |